< Previous | Main Contents | Section Contents | Next >
BUILDING (SCOTLAND) ACT 2003 CONSULTATION ON BUILDING REGULATIONS
AND GUIDANCE DOCUMENT: NON DOMESTIC
|
|
Annex 6.C U-values of ground floors and basements
6.C.0 Introduction
6.C.1 Example of how to use tables
6.C.2 Solid ground floors
6.C.3 Suspended ground floors
6.C.4 Basement floors
6.C.5 Basement walls
|
|
annex 6.C
|
U-values of ground floors and basements
[Appendix C]
|
|
Insulation not Necessary
|
6.C.0 Introduction
A ground floor of a non-domestic building should not
have a U-value exceeding 0.25 W/m2K, if the Elemental
Method is to be used (subject to the carbon intensity of the heating).
This can normally be achieved without the need for insulation if the perimeter
to area ratio is less than 0.12 m/m2 for solid ground
floors or less than 0.09 m/m2 for suspended floors. However,
some ground floor insulation will be needed for the majority of buildings.
For basement floors the recommended Elemental U-value is also 0.25 W/m2K
but for basement walls it is 0.30 W/m2K (again both of
these figures are subject to the carbon intensity of the heating system).
For exposed floors and for floors over unheated spaces the reader is referred
to Annex B.
|
|
www.bsi-global.com
www.cibse.org
|
Full details about how to calculate the U-value of a
ground floor, a basement floor or a basement wall are given in BS EN ISO 13370
and in CIBSE Guide Section A3 (1999 edition). This Annex gives a summary
of how to determine the U-value which will suffice for most common constructions.
|
|
Soil type
|
For ground floors and basements the U-value depends upon
the type of soil beneath the building. Where the soil type is unknown,
clay soil should be assumed as this is the most typical soil type in the
UK. The tables which follow refer to this soil type. Where the soil is
not clay or silt, the U-value should be calculated using the procedure
in BS EN ISO 13370.
|
|
Calculation of areas
Extensions
|
Floor dimensions should be measured in accordance with
6.0.10. In the case of semi-detached or terraced premises and similar,
for example a row of industrial units, the floor dimensions can either
be taken as those of the premises themselves, or of the whole building.
When considering extensions to existing buildings the floor dimensions
may be taken as those of the complete building including the extension.
|
|
www.bre.co.uk
|
Care should be taken to avoid thermal bridging at the
floor edge. See BRE Report BR262 "Thermal insulation: avoiding
risks".
|
|
Areas outwith the insulation envelope
|
Unheated spaces outside the insulated fabric, such as
attached garages or porches, should be excluded when determining the perimeter
and area but the length of the wall between the heated building and the
unheated space should be included when determining the perimeter.
|
|
Interpolation
|
The following tables have been derived from BS EN ISO 13370.
For the purposes of Section 6 it will be sufficient to derive the U-values
from the tables using linear interpolation where appropriate.
|
| |
6.C.1 Example of how to obtain U-values from the
tables
The following example shows how to use Table 1 for a
solid ground floor and serves as an illustration of how to use the tables
supplied in this Annex, interpolating between appropriate rows or columns.
A proposed building has a perimeter of 38.4 m and
a ground floor area of 74.25 m2. The floor construction
consists of a 150 mm concrete slab, 75 mm of rigid insulation
(thermal conductivity 0.04 W/mK) and a 65 mm screed. Only the
insulation layer is included in the calculation of the thermal resistance.
|
| |
The perimeter to area ratio is equal to 38.4 ¸ 74.25
= 0.517 m/m2. Table C.1 gives values for perimeter/area
ratios of 0.50 and 0.55 but not for any values between 0.50 and 0.55.
In this case, the U-value corresponding to a perimeter to area ratio of
0.50 should be used since 0.517 is closer to 0.50 than to 0.55.
The thermal resistance of the insulation is obtained
by dividing the thickness (in metres) by the conductivity. The resistance
is then 0.075 ¸ 0.04 = 1.875 m2K/W.
The relevant part of Table C1 is shown below:
| |
Thermal resistance (m2K/W)
|
|
Perimeter/Area
|
1.5
|
2.0
|
|
0.50
|
0.33
|
0.28
|
|
| |
The U-value corresponding to a thermal resistance of
1.875 m2K/W is obtained by linear interpolation as below:

|
| |
The U-value of this ground floor is therefore 0.29 W/m2K.
Note: In the example for Table C.1 the appropriate
row was chosen and interpolation was carried out between the appropriate
columns. For all of the other tables, however, the appropriate column
in the table should be selected and interpolation should be carried out
between the appropriate rows.
|
|
Ground floors with all-over insulation or no insulation
|
6.C.2 Solid ground floors
Solid ground floors are taken to mean ground floors in
which there is no significant air layer separating the building from the
ground. Listed in the table below are U-values for solid ground floors.
U-values are given in the following table for various perimeter-to-area
ratios for a range of insulation levels. Where the floor is uninsulated
the column corresponding to a thermal resistance of 0 should be used.
Table 1: U-values for solid ground floors (W/m2K)
| |
Thermal resistance of all-over insulation (m2K/W)
|
|
Perimeter/Area
|
0
|
0.5
|
1.0
|
1.5
|
2.0
|
2.5
|
|
0.05
|
0.13
|
0.11
|
0.10
|
0.09
|
0.08
|
0.08
|
|
0.10
|
0.22
|
0.18
|
0.16
|
0.14
|
0.13
|
0.12
|
|
0.15
|
0.30
|
0.24
|
0.21
|
0.18
|
0.17
|
0.15
|
|
0.20
|
0.37
|
0.29
|
0.25
|
0.22
|
0.19
|
0.18
|
|
0.25
|
0.44
|
0.34
|
0.28
|
0.24
|
0.22
|
0.19
|
|
0.30
|
0.49
|
0.38
|
0.31
|
0.27
|
0.23
|
0.21
|
|
0.35
|
0.55
|
0.41
|
0.34
|
0.29
|
0.25
|
0.22
|
|
0.40
|
0.60
|
0.44
|
0.36
|
0.30
|
0.26
|
0.23
|
|
0.45
|
0.65
|
0.47
|
0.38
|
0.32
|
0.27
|
0.23
|
|
0.50
|
0.70
|
0.50
|
0.40
|
0.33
|
0.28
|
0.24
|
|
0.55
|
0.74
|
0.52
|
0.41
|
0.34
|
0.28
|
0.25
|
|
0.60
|
0.78
|
0.55
|
0.43
|
0.35
|
0.29
|
0.25
|
|
0.65
|
0.82
|
0.57
|
0.44
|
0.35
|
0.30
|
0.26
|
|
0.70
|
0.86
|
0.59
|
0.45
|
0.36
|
0.30
|
0.26
|
|
0.75
|
0.89
|
0.61
|
0.46
|
0.37
|
0.31
|
0.27
|
|
0.80
|
0.93
|
0.62
|
0.47
|
0.37
|
0.32
|
0.27
|
|
0.85
|
0.96
|
0.64
|
0.47
|
0.38
|
0.32
|
0.28
|
|
0.90
|
0.99
|
0.65
|
0.48
|
0.39
|
0.32
|
0.28
|
|
0.95
|
1.02
|
0.66
|
0.49
|
0.39
|
0.33
|
0.28
|
|
1.00
|
1.05
|
0.68
|
0.50
|
0.40
|
0.33
|
0.28
|
Note:
As an alternative to the above table, the methods described
in BS EN ISO 13370 may be used.
|
|
Ground floors with edge insulation
|
Where horizontal or vertical edge insulation is used
instead of all-over floor insulation, the U-value of the uninsulated floor
(obtained from the column corresponding to thermal resistance of 0 in
Table 1) is adjusted by adding Y ´ P/A to account for the effects
of edge insulation, where P/A is the perimeter (m) to area (m2)
ratio and Y is the edge insulation factor obtained from either Table
2 or 3 below. As Y ´ P/A is negative, the effect of this addition
will be a reduction in the U-value.
Table 2: Edge insulation factor (Y ) for horizontal
edge insulation
|
Insulation width (m)
|
Thermal resistance of insulation (m2K/W)
|
|
0.5
|
1.0
|
1.5
|
2.0
|
|
0.5
|
-0.13
|
-0.18
|
-0.21
|
-0.22
|
|
1.0
|
-0.20
|
-0.27
|
-0.32
|
-0.34
|
|
1.5
|
-0.23
|
-0.33
|
-0.39
|
-0.42
|
Table 3: Edge insulation factor (Y
) for vertical edge insulation
|
Insulation depth (m)
|
Thermal resistance of insulation (m2K/W)
|
|
0.5
|
1.0
|
1.5
|
2.0
|
|
0.25
|
-0.13
|
-0.18
|
-0.21
|
-0.22
|
|
0.50
|
-0.20
|
-0.27
|
-0.32
|
-0.34
|
|
0.75
|
-0.23
|
-0.33
|
-0.39
|
-0.42
|
|
1.00
|
-0.26
|
-0.37
|
-0.43
|
-0.48
|
Note:
When floors incorporate both all-over and edge insulation,
the procedure in BS EN ISO 13370 may be used.
|
|
Ground floors with no insulation
|
6.C.3 Suspended ground floors
The following table gives U-values of uninsulated suspended
floors for various perimeter to area ratios and for two levels of ventilation
(expressed in m2/m) below the floor deck. The data applies
to a floor deck at a height of not more than 0.5 m above the external
ground level where the wall surrounding the underfloor space is uninsulated.
Table 4: U-values of uninsulated
suspended floors
|
Perimeter to area ratio
|
Ventilation opening area per unit perimeter of
underfloor space (m2/m)
|
|
0.0015 m2/m
|
0.0030 m2/m
|
|
0.05
|
0.15
|
0.15
|
|
0.10
|
0.25
|
0.26
|
|
0.15
|
0.33
|
0.35
|
|
0.20
|
0.40
|
0.42
|
|
0.25
|
0.46
|
0.48
|
|
0.30
|
0.51
|
0.53
|
|
0.35
|
0.55
|
0.58
|
|
0.40
|
0.59
|
0.62
|
|
0.45
|
0.63
|
0.66
|
|
0.50
|
0.66
|
0.70
|
|
0.55
|
0.69
|
0.73
|
|
0.60
|
0.72
|
0.76
|
|
0.65
|
0.75
|
0.79
|
|
0.70
|
0.77
|
0.81
|
|
0.75
|
0.80
|
0.84
|
|
0.80
|
0.82
|
0.86
|
|
0.85
|
0.84
|
0.88
|
|
0.90
|
0.86
|
0.90
|
|
0.95
|
0.88
|
0.92
|
|
1.00
|
0.89
|
0.93
|
|
|
Suspended floors with insulation
|
Note: As an alternative to the above table, the methods
described in BS EN ISO 13370 may be used.
The U-value of an insulated suspended floor should be
calculated using:
U = 1 / [(1/U0 ) 0.2 + Rf]
where U0 is the U-value of an uninsulated
suspended floor obtained from Table 4, above or another approved method.
Rf, the thermal resistance of the floor deck, is determined
from Uf, the U-value of the floor deck, where:
and where Uf is calculated using the Combined
Method, as described in BS EN ISO 6946, assuming thermal
resistances of 0.17 m2K/W for both the upper and lower
surfaces of the floor deck.
|
|
Basement floors with no insulation
|
6.C.4 Basement floors
The U-value of an uninsulated basement floor should be
calculated by using Table 5 below, or the methods described in BS EN ISO 13370.
Table 5: U-values of uninsulated basement
floors
|
Perimeter to area ratio
|
Basement depth (m)
|
|
0.5
|
1
|
1.5
|
2
|
2.5
|
|
0.1
|
0.20
|
0.19
|
0.18
|
0.17
|
0.16
|
|
0.2
|
0.34
|
0.31
|
0.29
|
0.27
|
0.26
|
|
0.3
|
0.44
|
0.41
|
0.38
|
0.35
|
0.33
|
|
0.4
|
0.53
|
0.48
|
0.44
|
0.41
|
0.38
|
|
0.5
|
0.61
|
0.55
|
0.50
|
0.46
|
0.43
|
|
0.6
|
0.68
|
0.61
|
0.55
|
0.50
|
0.46
|
|
0.7
|
0.74
|
0.65
|
0.59
|
0.53
|
0.49
|
|
0.8
|
0.79
|
0.70
|
0.62
|
0.56
|
0.51
|
|
0.9
|
0.84
|
0.73
|
0.65
|
0.58
|
0.53
|
|
1.0
|
0.89
|
0.77
|
0.68
|
0.60
|
0.54
|
|
|
Basement floors with insulation
|
Determine the U-value of an insulated basement floor
from:
U = 1 / [(1/U0) + Rins]
where U0 is the U-value determined from Table
5 (or other approved method) for uninsulated basements and Rins
is the thermal resistance of the insulation in m2K/W. The value
of Rins may be calculated from the thickness of the insulation
divided by its conductivity.
6.C.5 Basement walls
Table 6 below gives the U-value of a basement wall for
a given basement depth and basement wall resistance.
Table 6: U-values of basement walls
|
Basement wall resistance (m2K/W)
|
Basement depth (m)
|
|
0.5
|
1
|
1.5
|
2
|
2.5
|
|
0.2
|
1.55
|
1.16
|
0.95
|
0.81
|
0.71
|
|
0.5
|
0.98
|
0.78
|
0.66
|
0.58
|
0.52
|
|
1.0
|
0.61
|
0.51
|
0.45
|
0.40
|
0.37
|
|
2.0
|
0.35
|
0.30
|
0.27
|
0.25
|
0.24
|
|
2.5
|
0.28
|
0.25
|
0.23
|
0.21
|
0.20
|
|
< Previous | Main Contents | Section Contents | Next > |