< Previous | Main Contents | Section Contents | Next >
BUILDING (SCOTLAND) ACT 2003 CONSULTATION ON BUILDING REGULATIONS
AND GUIDANCE DOCUMENT: NON DOMESTIC
|
|
6.2 Building fabric - limiting energy use
Functional standard
6.2.0 Introduction
6.2.1 Elemental Method
6.2.2 Heat Loss Method
6.2.3 Carbon Emissions Calculation Method
6.2.4 Limiting the effect of thermal bridging at junctions and
around openings
6.2.5 Limiting air infiltration
|
| standard
6.2
mandatory |
In order to comply with standard 6.1 every building
must be designed and constructed in such a way that the insulation envelope
resists thermal transfer.
Limitation
This standard does not apply to:
a. buildings, other than dwellings, which will not be heated nor cooled,
other than heating for the purpose of frost protection;
b. buildings which are ancillary to a dwelling and
which will not be heated other than heating for the purpose of frost protection.
|
| |
6.2.0 Introduction [J8.1]
The guidance in 6.2.1 to 6.2.3 gives three alternative
approaches to the design of the insulation envelope of a new non-domestic
building. These are:
- Elemental Method
- Heat Loss Method
- Carbon Emissions Calculation Method
With the Elemental Method and Heat Loss Method a building
fabric improvement is allowed against heating systems which have a high
carbon intensity (see 6.3), but in general the energy efficiency of the
building services are considered as separate issues. The Carbon Emissions
Calculation Method offers the most design flexibility. The principal advantages
of each approach are given in the preamble to each method. It is important
to refer to the Elemental Method in the first instance. This is because
the "trade-off" arrangements which are allowed by either the
Heat Loss or the Carbon Emissions Calculation Methods use a notional building
designed to the Elemental Method as a comparison.
|
| Conversions |
In the case of conversions, as defined by Regulation
3, the building as converted must be improved to as close to the full requirements
of this standard as is reasonably practicable, and in no case be worse than
before the conversion (Regulation 12, Schedule 6).
6.2.1 The Elemental Method [J8.2] [J8.3] [J8.4]
[CRD141]
This approach to designing the insulation envelope is the most basic
and it involves assessing the thermal transmittance through each element
of the building. As stated previously, with the Heat Loss or the Carbon
Emissions Calculation Methods, a notional building which is designed to
the Elemental Method, will be used as a comparison. The main benefit of
using this basic method is that there are a reduced number of calculations
to be carried out.
|
|
High carbon intensity heating systems
|
At an early stage a check should be done to ensure that
the form and fabric does not result in excessive cooling being needed
for the building (see 6.6.1). Also, if the heating system has a high carbon
intensity the U-values will need to be improved (see 6.3.2).
|
|
Where heating type is unknown
|
When the type of heating system for a building is not
known at the time of making the building warrant application, for example
a staged warrant application, a high carbon intensity for the system should
be assumed. U-values that have been modified by following the guidance
in 6.3.2 should be adopted.
|
|
Objective
|
To use the Elemental Method, individual exposed building
elements and other elements forming the insulation envelope of
a building should have U-values which do not exceed the numerical value
given in Table 1. Also the percentage areas of windows, doors and rooflights
should not exceed those indicated in Table 2. It should be noted that
Annex 6.P can be used instead of Table 1,
if the building is of limited-life and does not contain sleeping accommodation.
Table 1: Maximum recommended U-values for building elements
forming part of the insulation envelope
|
Pitched roof
With insulation between rafters
|
0.20
|
|
Pitched roof
With insulation between ceiling ties or collars
|
0.16
|
|
Flat roof or roof with integral insulation
|
0.25
|
|
Exposed wall, external wall or wall referred to in 6.0.5
|
0.30
|
|
Exposed floor or floor referred to in 6.0.5
|
0.25
|
|
Vehicle access and similar large doors. (Including doors located
in walls referred to in 6.0.5)
|
0.7
|
|
Windows, other doors and rooflights (area-weighted average), glazing
in metal frames. (Including glazing and doors located in walls referred
to in 6.0.5)
|
2.2
|
|
Windows, other doors and rooflights (area-weighted average), glazing
in wood or plastic frames. (Including glazing and doors located
in walls referred to in 6.0.5)
|
2.0
|
|
| |
When reading Table 1, above, the following points should
be taken into account:
- A wall excludes any glazing (including windows), doors and their associated
frames.
- A roof excludes any glazing and associated frames (including roof
windows and rooflights). This is not considered applicable however,
where such glazing only provides daylight to a roofspace where the thermal
insulation material is located between the ceiling ties or collars.
- Individual U-values for windows, doors and rooflights may vary however
the average U-value for all windows, doors and rooflights should not
be more than the figure shown. Trade-off should only occur between elements
in the same frame classification: i.e. (1) wood and plastic or (2) metal.
For method of calculation see Annex 6.E.
- Metal-framed windows have slimmer frames and therefore give a passive
solar benefit and this justifies a less demanding level of U-value.
- No maximum U-value necessary for vehicle access and similar large
doors which for operational reasons, have to be left open when the building
is in use.
- No maximum U-value necessary for shop entrances and shop display windows
which are situated at an access level.
Table 2: Maximum recommended percentage areas of windows,
doors and rooflights in the insulation envelope
|
Types of building
|
Windows and doors expressed as a % of the insulation envelope
wall area (Total overall elevation)
|
Rooflights expressed as a % of the roof area
(Total overall surface area)
|
|
Residential (non-domestic)
|
30
|
20
|
|
Offices, shops and buildings for entertainment and assembly purposes
|
40
|
20
|
|
Industrial and storage buildings
|
15
|
20
|
|
|
Next stages
|
When reading Table 2, above, it should be noted that
the minimum percentage areas do not apply to:
- Vehicle access and other similar large doors.
- Shop entrances and shop display windows at an access level.
- Separating walls that follow the guidance in 6.0.6.
Once the U-values for the insulation envelope have been
established by this method, the following issues should be considered:
- Limiting the effect of thermal bridging at junctions and around openings
that occur in the insulation envelope. (see 6.2.4)
- Limiting air infiltration at the insulation envelope. (see 6.2.5)
- Energy efficiency of the space heating and hot water system, including
any improvement in the average U-value due to the high carbon intensity
of the heating system (see 6.3 and 6.4)
- Energy efficiency of the artificial lighting (see 6.5)
- Energy efficiency of any air conditioning or mechanical ventilation
system (see 6.6)
- Commissioning of the building services (see 6.7)
- Written information (see 6.8).
|
|
High carbon intensity heating systems
|
6.2.2 The Heat Loss Method [J8.5] [J8.6]
This approach allows greater flexibility with the design
of the insulation envelope than is given with the Elemental Method. The
principal benefit of using this Method is that it allows the higher U-values
for parts of the insulation envelope to be compensated by lower U-values
for other parts of the construction. A worked example of this calculation
is given in Annex 6.J. Similar to the Elemental
Method, at an early stage a check should be done to ensure that the form
and fabric does not result in excessive cooling being needed for the building
(see 6.6.1). Also, if the heating system has a high carbon intensity,
the U-values will need to be improved (see 6.3.2). This adjustment is
done by using more demanding U-values in the notional building that is
formed as a part of the calculation process.
|
|
Objective
|
To use the Heat Loss Method, the insulation
envelope of a non-domestic building should have a total rate of heat loss
which is not greater than that which would occur from a notional building
(of the same size and shape) which follows the guidance given for the
Elemental Method.
|
|
Proposed building
|
In the first instance, use a copy of Worksheet 6.J.4
(see Annex 6.J) and in conjunction with
the table below, establish by calculation the total rate of heat loss
from the proposed building.
Maximum recommended U-values when trading off between building
elements in Heat Loss Method
|
Building element forming part of insulation envelope
|
Maximum U-value (W/m2K) (subject to Note
below)
|
|
Roof
|
0.45
|
|
Wall or floor (except where zero thermal transmittance occurs)
|
0.70
|
|
Windows, doors and rooflights
|
No limit
|
|
| |
Note:
- If the total area of windows, doors and rooflights in the proposed
building is less than the total maximum area recommended in
Table 2 to 6.2.1, then the average U-value of the roof, wall
or floor should not exceed the appropriate value given in Table 1 to
6.2.1 by more than 0.02 W/m2K. Annex
6.P can be used instead of Table 1 to 6.2.1, if the building is
of limited-life and does not contain sleeping accommodation. This simple
constraint helps to reduce the incidence of buildings being designed
without regard to natural daylight and the energy efficiency implications
from excessive use of artificial lighting.
- Only a half of the permitted rooflight area in Table 2 to 6.2.1 can
be converted into an increased area of window and doors.
|
|
Notional building
|
After the total rate of heat loss has been established for the proposed
building, this process should be repeated but this time demonstrating
the total rate from the notional building. To do this, the appropriate
U-values obtained from Table 1 to 6.2.1 (or if appropriate Annex
6.P) should be inserted into a further copy of Worksheet 6.J.4.
|
|
Where heating type is unknown
|
When the type of heating system for a building is not
known at the time of making the building warrant application, for example
a staged warrant application, a high carbon intensity for the system should
be assumed. The U-values inserted into Worksheet 6.J.4 should be those,
that have been modified by following the guidance in 6.3.2.
When creating the notional building insulation envelope
for comparison purposes, the maximum percentage area for windows, doors
and rooflights in Table 2 to 6.2.1 should be used. In establishing the
total rate of heat loss from the notional building, the following constraints
should be applied:
- The insulation envelope of the notional building is to be the same
size and shape as that for the proposed building
- Vehicle access/similar large doors which for operational reasons,
have to be left open when the building is in use and also shop
entrances and shop display windows at an access level should be of the
same area and U-value as those in the proposed building. This is principally
because the percentage area of such openings and their U-value are unrestricted
in the elemental method.
- If, with no added insulation, the U-value of a floor next
to the ground in the proposed building is less than the value
given in Table 1 to 6.2.1 (or if appropriate Annex
6.P), then that lower value should be used for the notional building.
This prevents an inequitable trade off being obtained, which would be
based solely on the fortuitous "footprint" size of the building.
|
|
Comparison
|
The total rates of heat loss from both the proposed and
the notional buildings, should be compared. If the proposed building total
rate is less than or equal to the notional building, the design is satisfactory.
|
|
Next stages
|
Once the U-values for the insulation envelope have been
established by this method, the following issues should be considered:
- Limiting the effect of thermal bridging at junctions and around openings
that occur in the insulation envelope. (see 6.2.4)
- Limiting air infiltration to the insulation envelope. (see 6.2.5)
- Energy efficiency of the space heating and hot water system, including
any improvement in the average U-value due to the high carbon intensity
of the heating system (see 6.3 and 6.4)
- Energy efficiency of the artificial lighting (see 6.5)
- Energy efficiency of any air conditioning or mechanical ventilation
system (see 6.6)
- Commissioning of the building services (see 6.7)
- Written information (see 6.8).
|
| |
6.2.3 The Carbon Emissions Calculation Method [J8.7][J8.8]
[J8.9]
This method allows most flexibility in the design of
the building and enables the energy efficiency of the building services
to be taken into consideration. The annual carbon emissions for the proposed
building are compared with those from a notional building. This method
can be used to take advantage of solar heat gains and electricity generated
from low carbon technologies that are either building integrated or perhaps
exclusive to the building or group of buildings, photovoltaic cladding
or wind turbines, for example. An integrated approach can be adopted and
the following parts of this guidance may be ignored for the design of
the proposed building:
- Energy efficiency of the space heating and hot water system (see 6.3
and 6.4)
- Energy efficiency of the artificial lighting (see 6.5)
Energy efficiency of any air conditioning or mechanical
ventilation system (see 6.6)
|
|
Objective
|
To use the carbon emissions calculation method, the annual
carbon emissions of a non-domestic building should be no greater
than that which would occur from a notional building. This notional building
should comply with the Elemental Method and also the guidance given on
energy efficiency of the building services systems. It should also be
of the same size and shape as the proposed building.
|
|
Proposed building
|
Although this method allows greater freedom of design,
there are constraints placed on the insulation envelope these are:
- The guidance in this document for limiting thermal bridging at junctions
and around openings and for limiting air infiltration should be applied.
- The U-values in the table below should not be exceeded.
Maximum recommended U-values when trading
off between building elements in the Carbon Emissions Calculation
Method
|
Building element forming part of
insulation envelope
|
Maximum U-value (W/m2K)
|
|
Roof
|
0.45
|
|
Wall or floor (except where zero thermal transmittance occurs)
|
0.70
|
|
Windows, doors and rooflights
|
No limit
|
|
|
Notional building
|
The following constraints should be applied to the notional
building created using the Elemental Method:
- The insulation envelope of the notional building is to be the same
size and shape as that for the proposed building
- Vehicle access/similar large doors which for operational reasons,
have to be left open when the building is in use and also shop
entrances and shop display windows at an access level should be of the
same area and U-value as those in the proposed building. This is principally
because the percentage area of such openings and their U-value are unrestricted
in the elemental method.
- If, with no added insulation, the U-value of a floor next
to the ground in the proposed building is less than 0.25 W/m2K,
then that lower value should be used for the notional building.
This prevents an inequitable trade off being obtained, which would be
based on the fortuitous "footprint" size of the building.
|
|
Calculation procedure
|
The Carbon Emissions Calculation Method can be carried
out by using a calculation procedure that:
- has been tested satisfactorily against available benchmark tests as
described in CIBSE Application Manual Building Energy and Environmental
Modelling, AM11, 1998; and
- has been accepted by the submitting organisation as having satisfied
their in-house quality assurance procedures, for example by submitting
with the calculations a completed and signed copy of Annex B to AM11:
Checklist for choosing BEEM software, showing that the software
used is appropriate for the purpose to which it has been applied.
|
|
Next stages
|
Once the U-values for the insulation envelope and the energy efficiency
of the building services have been established by this method, the following
issues should be considered:
- Limiting the effect of thermal bridging at junctions and around openings
that occur in the insulation envelope. (see 6.2.4)
- Limiting air infiltration to the insulation envelope. (see 6.2.5)
- Commissioning of the building services (see 6.7)
- Written information (see 6.8).
6.2.4 Limiting the effect of thermal bridging at junctions and
around openings [J9.1]
The insulation envelope of the non-domestic building
should be constructed in such a way that there are no substantial thermal
bridges or gaps where the layers of insulation occur. Significant in-use
energy consumption can occur, through incorrect detailing at the design
stage or careless construction on site. The key areas of concern are:
- Within building elements
- At the junction between building elements
- At the edges of building elements where openings in the structure
are formed.
|
|
www.bre.co.uk
|
One approach to addressing these issues would be to follow
the advice given in the Building Research Establishment (BRE) Report 262
Thermal insulation, avoiding risks 2002 edition. Another
way, could be to demonstrate equivalent performance by calculation.
Annex 6.D gives a procedure for establishing condensation risk and
heat loss at the edges of openings.
6.2.5 Limiting air infiltration [J10.1]
All building fabric will allow a certain degree of air
leakage. It is widely recognised that it is impossible to make the insulation
envelope 100% airtight. Where it is desirable to either vent or ventilate
the building fabric to the outside air (to allow moisture due to either
precipitation or condensation to escape), this should be designed into
the construction. Reliance on fortuitous ventilation should be avoided.
Measures should be introduced however, to reduce unwanted air leakage
and thereby prevent an increase in energy use within the heated or cooled
part of the building. The guidance given here should not be used to compromise
ventilation required for:
- Health of the building occupants
- Any smoke control system
- Combustion appliances
The main principle of limiting air infiltration is to
provide a continuous barrier to air movement around the insulation envelope
and thereby reduce external air paths into each of the following:
- The inside of the building
- The internal building elements
- The "warm" side of the insulation
- Spaces between the component parts of exposed building elements, where
such parts contribute significantly to the thermal performance of the
element.
Other areas of the building that need consideration are
entrances to the building and shafts which extend through most of the
floors (e.g. lift or stair enclosures).
Correct cavity barrier design for the purposes of structural
fire precautions, with airtight materials, can often contribute to achieving
this objective.
One approach to addressing these issues would be to follow
the advice given in the Building Research Establishment (BRE) Report BR
448 2002 edition Airtightness in Commercial and Public
Buildings.
BR 448 gives examples of appropriate design details and
construction practice, but alternative details can be used if
equivalent performance can be demonstrated.
|
< Previous | Main Contents | Section Contents | Next > |