|
6.0.6 Zero thermal transmittance and the insulation
envelope [J2.4]
Thermal transmittance through separating walls
or separating floors between 2 units in different occupation
should be ignored, if it is likely that both parts will be heated or cooled
to a similar degree.
6.0.7 Roofs that perform the function of a floor
[J2.2]
For the purposes of establishing the exposed building
element status, a roof of a building that also performs the function of
a floor or similar load-bearing surface (e.g. an access deck, escape route,
roof garden or car park), should be considered as a roof.
6.0.8 Atria [J2.3]
In a building with an atrium, the guidance given in 6.0.5
above, only applies if the atrium is unheated and totally divided from
the remainder of the building by, glazing and doors and if appropriate,
walls and floors. In addition to this, it should not be intended that
the atrium is to gain heat transfer from the surrounding building. In
other situations involving atria, where none of this occurs, the insulation
envelope is at roof level (usually predominantly glazed) and the atria
is considered to be a part of the main building.
6.0.9 Annexes to guidance
At the back of the main guidance document are the Annexes.
These have a dual role. Some give guidance in respect of calculation procedures.
Others however, show how the guidance should be applied to buildings in
the form of, alterations, extensions, historic buildings and conversions.
6.0.10 Calculation of areas [J2.5]
When calculating areas, for the purposes of this Section and in addition
to Regulation 7, Schedule 4, the following should be observed:
- All areas should be measured in m2, unless stated otherwise
in the guidance.
- The area of a floor, wall or roof is to be measured between finished
internal faces of the insulation envelope, including any projecting
bays and in the case of a roof, in the plane of the insulation.
- Floor areas are to include stairwells within the insulation envelope
and also non-useable space (for example service ducts).
- The area of an opening should be measured internally from ingo to
ingo and from head to sill or threshold.
6.0.11 Latest changes
The Circular referred to in Standard 6.1 is required
due to the change from mandatory Technical Standards to Guidance.
Heating system Standard 6.3. The previous Technical
Standards only permitted heating systems with a higher carbon intensity
(e.g. electric resistance heating) in a building by way of a tortuous
route through the Carbon Emissions Calculation Method. Clause 6.3.2 now
gives a trade-off against building fabric and can be used with either
the Elemental Method or the Heat Loss Method.
Annex 6.H on alterations
and extensions is provided to help building designers and building control
officers determine an appropriate approach to dealing with building work
to existing buildings that are currently less than ideal in terms of energy
efficiency. One significant addition is that instead of heating systems
with a higher carbon intensity being prevented from being installed in
an existing building, it is now possible to compensate by upgrading the
fabric insulation.
Annex 6.N on conversions
is provided to help building designers and building control officers determine
an appropriate approach to dealing with conversions to existing buildings
that are currently less than ideal in terms of energy efficiency. One
significant addition is that buildings that are converted (schedule 2),
and also which were heated in their existing state) should meet certain
levels of fabric insulation.
|