Example 1 - Pitched roof with insulation between ceiling joists or between rafters
Determine the thickness of the insulation layer required to achieve a U-value of:
0.25 W/m2K if insulation is between the joists, and
0.35 W/m2K if insulation is between the rafters.
diagram
For insulation placed between ceiling joists (U-value 0.25 W/m2K)
Using Table E1, from column D, row 2 of the table, the base thickness of insulation required is 170 mm.
The base thickness may be reduced by taking account of the other materials as follows from Table E4:
|
19 mm roof tiles |
column D, row 13 |
= 1 mm |
|
Roof space |
column D, row 11 |
= 5 mm |
|
10 mm plasterboard |
column D, row 7 |
= 2 mm |
|
Total reduction |
= 8 mm |
The minimum thickness of the insulation layer between the ceiling joists required
to achieve a U-value of
0.25 W/m2K is therefore:
Base thickness less total reduction ie 170 _ 8 = 162 mm.
For insulation placed between rafters (U-value 0.35 W/m2K)
Using Table E1, from column D, row 4 in the table, the base thickness of insulation required is 103 mm.
The reductions in the base thickness are obtained as follows from Table E4:
|
19 mm roof tiles |
column D, row 13 |
= 1 mm |
|
10 mm plasterboard |
column D, row 7 |
= 2 mm |
|
Total reduction |
= 3 mm |
The minimum thickness of the insulation layer between the rafters required to achieve a U-value of 0.35 W/m2K is therefore:
Base thickness less total reduction ie 103 3 = 100 mm.
Example 2 - Pitched roof with insulation between and over ceiling joists
Determine the thickness of the insulation layer above the joists required to achieve a U-value of 0.25 W/m2K for the roof construction shown below:
diagram
It is proposed to use mineral fibre insulation between and over the joists with a thermal conductivity of 0.035 W/mK.
Using Table E2, from column E, row 2 of the table, the base thickness of insulation layer = 152mm.
The base thickness may be reduced by taking account of the other materials as follows from Table E4:
|
19 mm roof tiles |
column E, row 13 |
= 1 mm |
|
Roof space |
column E, row 11 |
= 6 mm |
|
10 mm plasterboard |
column E, row 7 |
= 2 mm |
|
Total reduction |
= 9 mm |
The minimum thickness of the insulation layer over the joists required in addition to the 100 mm insulation between the joists to achieve a U-value of 0.25 W/m2K is therefore:
Base thickness less total reduction ie 152 100 9 = 43 mm.
Example 3 - Industrial roof with outer sheeting
Determine the thickness of the insulation layer required to achieve a U-value of 0.45 W/m2K for the roof construction shown below.
diagram
Using Table E3, from column E, row 6 of the table, the base thickness of the insulation layer is 73 mm.
The base thickness may be reduced by taking account of the other materials as follows from Table E4:
|
Outer sheeting (negligible) 12 mm Calcium Silicate liner board |
column E, row 10 |
= 2 mm |
|
Total reduction from base level thickness |
=2 mm |
|
The minimum thickness of the insulation layer required to achieve a U-value of 0.45 W/m2K is therefore:
Base thickness less total reduction ie 73 2 = 71 mm.
Example 4 - Concrete deck roof
Determine the thickness of the insulation layer required to achieve a U-value of 0.45 W/ m2K for the roof construction shown below.
diagram
Using Table E3, from column D, row 6 of the table, the base thickness of the insulation layer is 62 mm.
The base thickness may be reduced by taking account of the other materials as follows from Table E4:
|
3 layers of felt |
column D, row 14 |
= 1 mm |
|
|
150mm concrete deck column D, row 3 |
= 14 mm |
||
|
Total reduction from base level thickness |
= 15 mm |
||
The minimum thickness of the insulation layer required to achieve a U-value of 0.45 W/m2K is therefore:
Base thickness less total reduction ie 62 - 15 = 47 mm.
Table E5 to Part J Appendix E: Base thickness of insulation layer
|
Thermal conductivity of insulant (W/mK) |
||||||||
|
0.02 |
0.025 |
0.03 |
0.035 |
0.04 |
0.045 |
0.05 |
||
|
Design U-value |
Base thickness of insulating material (mm) |
|||||||
|
A |
B |
C |
D |
E |
F |
G |
H |
|
|
1 |
0.30 |
63 |
79 |
95 |
110 |
126 |
142 |
158 |
|
2 |
0.35 |
54 |
67 |
80 |
94 |
107 |
120 |
134 |
|
3 |
0.40 |
46 |
58 |
70 |
81 |
93 |
104 |
116 |
|
4 |
0.45 |
41 |
51 |
61 |
71 |
82 |
92 |
102 |
|
5 |
0.60 |
30 |
37 |
45 |
52 |
59 |
67 |
74 |
Table E6 to Part J Appendix E: Allowable reduction in base thickness for common components
|
Thermal conductivity of insulant (W/mK) |
||||||||
|
0.02 |
0.025 |
0.03 |
0.035 |
0.04 |
0.045 |
0.05 |
||
|
Design Component |
Reduction in base thickness of insulating material (mm) |
|||||||
|
A |
B |
C |
D |
E |
F |
G |
H |
|
|
1 |
Cavity (25 mm min.) |
4 |
5 |
5 |
6 |
7 |
8 |
9 |
|
2 |
Outer leaf brick |
2 |
3 |
4 |
4 |
5 |
6 |
6 |
|
3 |
13 mm plaster |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
4 |
13 mm lightweight plaster |
2 |
2 |
2 |
3 |
3 |
4 |
4 |
|
5 |
10 mm plasterboard |
1 |
2 |
2 |
2 |
3 |
3 |
3 |
|
6 |
13 mm plasterboard |
2 |
2 |
2 |
3 |
3 |
4 |
4 |
|
7 |
Airspace behind |
|||||||
|
plasterboard dry-lining |
2 |
3 |
3 |
4 |
4 |
5 |
6 |
|
|
8 |
9 mm sheathing ply |
1 |
2 |
2 |
2 |
3 |
3 |
3 |
|
9 |
20 mm cement render |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
|
10 |
13 mm tile hanging |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
Table E7 to Part J Appendix E: Allowable reduction in base thickness for concrete components
|
Thermal conductivity of insulant (W/mK) |
||||||||
|
0.02 |
0.025 |
0.03 |
0.035 |
0.04 |
0.045 |
0.05 |
||
|
Density |
Reduction in base thickness of insulation (mm) |
|||||||
|
A |
B |
C |
D |
E |
F |
G |
H |
|
|
Concrete inner leaf |
||||||||
|
1 |
600 |
9 |
11 |
13 |
15 |
17 |
20 |
22 |
|
2 |
800 |
7 |
9 |
11 |
13 |
15 |
17 |
19 |
|
3 |
1000 |
6 |
8 |
9 |
11 |
12 |
14 |
15 |
|
4 |
1200 |
5 |
6 |
7 |
9 |
10 |
11 |
12 |
|
5 |
1400 |
4 |
5 |
6 |
7 |
8 |
9 |
9 |
|
6 |
1600 |
3 |
4 |
4 |
5 |
6 |
7 |
7 |
|
Concrete outer leaf or single leaf wall |
||||||||
|
7 |
600 |
8 |
10 |
13 |
15 |
17 |
19 |
21 |
|
8 |
800 |
7 |
8 |
10 |
12 |
14 |
15 |
17 |
|
9 |
1000 |
6 |
7 |
8 |
10 |
11 |
12 |
14 |
|
10 |
1200 |
4 |
6 |
7 |
8 |
9 |
10 |
11 |
|
11 |
1400 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
|
12 |
1600 |
3 |
3 |
4 |
5 |
5 |
6 |
7 |
|
13 |
1800 |
2 |
3 |
3 |
4 |
4 |
5 |
5 |
|
14 |
2000 |
2 |
2 |
2 |
3 |
3 |
4 |
4 |
|
15 |
2400 |
1 |
1 |
2 |
2 |
2 |
2 |
3 |
Table E8 to Part J Appendix E: Allowable reduction in base thickness for insulated timber frame walls
|
Thermal conductivity of insulant (W/mK) |
||||||||
|
0.02 |
0.025 |
0.03 |
0.035 |
0.04 |
0.045 |
0.05 |
||
|
Thermal conductivity of insulation within frame (W/mK) |
Reduction in base thickness of insulation for each 100 mm of frame (mm) |
|||||||
|
A |
B |
C |
D |
E |
F |
G |
H |
|
|
1 |
0.035 |
42 |
53 |
63 |
74 |
84 |
95 |
105 |
|
2 |
0.040 |
38 |
48 |
58 |
67 |
77 |
87 |
96 |
Note:
The table is derived for walls for which the proportion of timber is 12%, which corresponds to 48 mm wide studs at 400 mm centres For other proportions of timber the U-value can be calculated using the procedure in Appendix A.